Common inspection cycles
This summary comes from a fire protection vendor's overview of the NFPA cycles. It isn't the code itself. Your local authority and the edition it enforces take priority, and they may add requirements.1
| System | Standard | Common intervals |
|---|---|---|
| Fire alarm | NFPA 72 | Panel daily or weekly, control equipment monthly, batteries and initiating devices semi-annually |
| Sprinklers and standpipes | NFPA 25 | Gauges and valves weekly or monthly, alarm devices quarterly, annual checks, internal obstruction check every 5 years |
| Portable extinguishers | NFPA 10 | Monthly visual check, annual inspection, 6-year maintenance or hydrotest where due |
| Kitchen hood suppression | NFPA 17A | Monthly owner checks, semi-annual system inspection |
| Clean agent systems | NFPA 2001 | Field devices semi-annually, enclosure annually, cylinders every 5 years |
| Emergency lights and exit signs | See your local code | Monthly 30-second test, annual 90-minute test |
Who does what
| Task | Usually done by |
|---|---|
| Scheduling, tracking and records | Property manager |
| Weekly and monthly visual checks | On-site staff, if they're trained and logged |
| Testing and certified inspection | A licensed fire protection contractor |
| Approving and paying for repairs | Manager, within limits, or owner |
| In-suite items | Depends on the lease. Spell it out |
| Enforcement and interpretation | Your local fire marshal or authority |
The records to keep
- A master calendar for each building and system, with due dates and the responsible party
- Signed inspection and test reports for each visit
- A deficiency log showing the date found, severity, repair and proof of completion
- Impairment notices when a system is out of service
- Contractor licenses and certificates of insurance
- Copies of letters or citations from authorities, and how each was resolved
The deficiency log deserves the most attention. An inspection that finds a problem and doesn't lead to a repair leaves you with a written record of a known issue.
Where owners get caught
- An inspection is confused with compliance. The visit happened, but the failed items stayed open.
- Access gaps. Devices in locked tenant suites go untested, and reports list them as "no access".
- Impairments aren't handled. When a system is down, you may need to notify the authority and your insurer, and take interim measures.
- Tenant build-outs. New walls can affect sprinkler coverage and alarm devices.
- A manager change. Records can get lost in a takeover, so put them on the document list.
Why asset managers should care
These items sit at the top of any priority list. In our deferred maintenance guide, life safety is the first category, and it's the one that shouldn't be deferred. A building's insurer, lender or next buyer may ask to see these records as well. Include the status in your quarterly review: inspections due, inspections overdue, open deficiencies and the age of the oldest one.
On our managed properties, our AI tracks compliance items so they don't depend on someone's memory, and our team handles the exceptions. Licensed contractors still do the inspections and testing.